Power To Go!  How many days can you afford to be without power?
 What is Power To Go?  Products  Wattage Calculator  Conact Us  More Info

Guaranteed Power - Guaranteed Fuel - Convenient Storage - Get Money Back

  
 

Generator, Towable 504 kW (PTG XP500)



Specs (Specifications may change due to continuous product development)

Click here for complete and printable specifications



XP500 SAE Specifications
Generator Ratings
Standby Rating
Prime Rating
Alternator
Voltage
Ph
Hz
kW/kVA
Amps
kW/kVA
Amps
120/208
3
60
470/587
1,633
460/575
1,596
127/220
3
60
500/625
1,642
462/577
1,514
120/240
3
60
470/587
1,415
460/575
1,383
HCI 544D
139/240
3
60
513/641
1,543
464/580
1,395
277/480
3
60
513/641
772
464/580
698
347/600
3
60
513/641
617
464/580
558

Fuel Consumption (60 Hz)
Diesel gal/hr (L/hr)
Standby Rating
100%
34.6 (130.78)
75%
26.3 (99.41)
50%
19.4 (73.33)
25%
10.4 (39.31)
Diesel gal/hr (L/hr)
Prime Power Rating
100%
30.6 (115.66)
75%
23.2 (87.69)
50%
17.2 (65.00)
25%
9.2 (34.77)

Dimensions
Length, inches (mm)
177.16 (4,500)
Width, inches (mm)
70.8 (1,800)
Height, inches (mm)
96.08 (2,440)
Weight, Radiator Mounted Model, Wet, lbs. (kg)
11,605 (5,275
Fuel Tank Capacity, gallons (liters)
211.6 (800)